ATyS p M 4P - set (125 A, 230/400 V AC)
Article number: 70 745- ATyS p M are 4 pole modular automatic transfer switches with an integrated controller.
- Their primary function is to switch between the main and backup supply in case of power failure. They work in automatic mode, if necessary the devices can be switched manually.
- They are designed for low voltage power supply systems with a maximum current of 40 to 160 A for applications where a short outage of the power supply is acceptable during transfer.
- They allow the setting of overvoltage, undervoltage and frequency thresholds.
- They are set using a display with precise input of individual values. In addition, they are equipped with a switching contact for generator control and user programmable inputs and outputs.
- ATyS p M - the set consists of the basic ATyS p M device, terminal shrouds, auxiliary contacts and bridging bar. The set therefore contains all necessary accessories for the selected model.
| Designed for power supply systems | 230/400 V AC | |
| Number of poles | 4 | |
| Rated load current | IL | 125 A |
| Frequency | f | 50 ÷ 60 Hz |
| Power consumption | P | 6 VA |
| Supply voltage range | 160 ÷ 305 V | |
| Rated impulse withstand voltage | Uimp | 6 kV |
| Switching time I-0 or II-0 | 45 ms | |
| Switching time I-II or II-I | 180 ms | |
| Lifetime (number of changeovers) | 10 000 | |
| Changing settings | Using the display and buttons | |
| Equipped with display | Yes (OLED technology) | |
| Recommended cross-section of connecting wires | S | 10 ÷ 70 mm2 |
| Power conductor stripping length | 15 | |
| Tightening torque | 5 | |
| Installation | On DIN rail 35 mm, On the mounting plate | |
| Operating position | Any | |
| Operating temperature | ϑ | - 20 ÷ 60 °C |
| Recommended fuse protection | 125 A/gG |