ATyS p M 4P - set (125 A, 230/400 V AC)

Article number: 70 745
  • ATyS p M are 4 pole modular automatic transfer switches with an integrated controller.
  • Their primary function is to switch between the main and backup supply in case of power failure. They work in automatic mode, if necessary the devices can be switched manually.
  • They are designed for low voltage power supply systems with a maximum current of 40 to 160 A for applications where a brief interruption of the load supply is acceptable during transfer.
  • They allow the setting of overvoltage, undervoltage and frequency thresholds.
  • They are set using a display with precise input of individual values. In addition, they are equipped with a switching contact for generator control and user programmable inputs and outputs.
  • ATyS p M - the set consists of the basic ATyS p M device, terminal shrouds, auxiliary contacts and bridging bar. The set therefore contains all necessary accessories for the selected model.
Designed for power supply systems 230/400 V AC
Number of poles
Rated load current IL 125 A
Frequency f 50 ÷ 60 Hz
Power consumption P 6 VA
Supply voltage range 160 ÷ 305 V
Rated impulse withstand voltage Uimp 6 kV
Switching time I-0 or II-0 45 ms
Switching time I-II or II-I 180 ms
Lifetime (number of changeovers) 10 000 
Changing settings Using the display and buttons
Equipped with display Yes (OLED technology)
Recommended cross-section of connected conductors S 10 ÷ 70 mm2
Operating temperature ϑ - 20 ÷ 60 °C
Recommended back-up fuse 125 A/gG
Installation On DIN rail 35 mm, On the mounting plate
Operating position Any
Tightening moment 5