DTE 2/485

Article number: 42 295
This product is no longer recommended for new designs, there may be a problem with its delivery in the future. Consider using an alternative product:
HDSP RS485
HDSP RS485
  • Designed for the protection of data and communication lines against longitudinal and transverse surge effects.
  • Contains both 1st and 2nd stage of protection.
  • Suitable for use in industrial applications, especially in low-voltage ESS, FDAS systems and also in measurement and control systems.
Testing category according to IEC 61643-21:2000 and EN 61643-21:2001 C1, C2, C3, D1
Number of pairs 2
Connector type Screw terminals
Rated operating DC voltage UN 0 ÷ 6 V
Maximum continuous operating voltage DC UC 7.2 V
Rated load current IL 0.1 A
Maximum discharge current (8/20) Imax 10 kA
C2 Nominal discharge current (8/20) In 1 kA
C2 Voltage protection level at In Up < 15 V
C3 Voltage protection level at 1 kV/μs Up < 9 V
D1 Impulse discharge current (10/350) line/PE Iimp 2.5 kA
D1 Total impulse discharge current (10/350) ITotal 5 kA
Response time tA < 30 ns
Data rate 1 Mbit/s
Bandwidth B 0 ÷ 1 MHz
Series impedance per line 2.2 Ω
Parasitic capacitance C < 1.5 nF
Lightning protection zone LPZ 0-1, LPZ 1-2, LPZ 2-3, LPZ3
Housing material Polyamid PA6, UL94 V-0
Degree of protection IP20
Operating temperature ϑ - 40 ÷ 70 °C
Clamp fastening range (solid conductor) 0.2 ÷ 2.5 mm2
Tightening moment 0,5
Installation On DIN rail 35 mm
Modular width 1
Operating position Any
Remote signalling No
Pluggable version No
QUICK CONTACT
Quick contact
Ing. Aneta Sčebelová