DTNVE 2/30/0,5

Article number: 42 309
  • Designed for the protection of data and communication lines against longitudinal and transverse surge effects.
  • The inserted series impedance consists of inductors, which allow the higher nominal current permanently flow through the protection. This predetermines the equipment for protection of the given power supply line of the system.
  • It can be used for the protection of analog data lines using the current loop 4 to 20 mA.
  • Not suitable for digital data transmission with high transmission speed.
Testing category according to IEC 61643-21:2000 and EN 61643-21:2001 C1, C2, C3, D1
Number of pairs 2
Connector type Screw terminals
Rated operating DC voltage UN 0 ÷ 30 V
Maximum continuous operating voltage DC UC 36 V
Rated load current IL 0.5 A
Maximum discharge current (8/20) Imax 10 kA
C2 Nominal discharge current (8/20) In 1 kA
C2 Voltage protection level at In Up < 75 V
C3 Voltage protection level at 1 kV/μs Up < 54 V
D1 Impulse discharge current (10/350) line/PE Iimp 2.5 kA
D1 Total impulse discharge current (10/350) ITotal 5 kA
Response time tA < 30 ns
Series inductance per line 4.7 μH
Parasitic capacitance C < 1.5 nF
Lightning protection zone LPZ 0-1, LPZ 1-2, LPZ 2-3, LPZ3
Housing material Polyamid PA6, UL94 V-0
Degree of protection IP20
Operating temperature ϑ - 40 ÷ 70 °C
Humidity range RH 5 ÷ 96 %
Recommended cross-section of connected conductors S 0.2 ÷ 2.5 mm2
Tightening moment 0,5
Installation On DIN rail 35 mm
Modular width 1
Operating position Any
Remote signalling No
Pluggable version No