HDSP 1GDT/70
Article number: 56 058- Designed for protection of shielding or insulated common reference wire of data, analogue or signal lines inside zones LPZ1 and higher.
- Suitable for increasing the degree of surge protection of data, analogue or signalling lines inside zones LPZ 1 and higher.
Testing category according to IEC 61643-21:2000 and EN 61643-21:2001 | C2, C3, B3 | |
Number of pairs | 1 | |
Connector type | Screw terminals | |
Maximum continuous operating voltage DC X5-9, X7-9 | UC | 70 V |
Rated load current | IL | 5 A |
C2 Nominal discharge current (8/20) | In | 5 kA |
Impulse discharge current (10/350) | Iimp | 1 kA |
B3 Voltage protection level X6-10, X8-10 at 100 V/μs | Up | < 550 V |
C3 Voltage protection level X6-10, X8-10 at 1 kV/μs | Up | < 700 V |
Lightning arrester arc voltage (at I> 1 A) | U | ~ 10 V |
Lightning arrester's glow discharge voltage | U | ~ 60 V |
Capacitance X6-8 | C | 8 pF |
Lightning protection zone | LPZ 1-2, LPZ 2-3, LPZ3 | |
Housing material | Polyamid PA6, UL94 V-0 | |
Degree of protection | IP20 | |
Operating temperature | ϑ | - 40 ÷ 70 °C |
Clamp fastening range (solid conductor) | 0.2 ÷ 4 mm2 | |
Tightening moment | 0,5 | |
Installation | On DIN rail 35 mm | |
Operating position | Any | |
Remote signalling | No | |
Pluggable version | No |