HDSP 2WS/24

Article number: 56 050
  • The 2WS/24 module can be used for protection of DC two-wire analogue or switching sensors (e.g. 4-20 mA, NO contact, NC contact). The 3WS/24 module is more suitable for protecting the input of a connected evaluating device.
  • Two-stage surge protection.
  • They are installed prior to the protected equipment and at the interface of LPZs 1 – 2 and higher.
  • They increase the EMC level of the connected equipment against switching and atmospheric transients.
  • They provide cable shield protection by limiting pulse overvoltage through a built-in 90 V gas discharge tube.
Testing category according to IEC 61643-21:2000 and EN 61643-21:2001 C2, C3, B3
Number of pairs 1
Connector type Screw terminals
Rated operating voltage DC of line X1-3 UN 0 ÷ 24 V
Maximum continuous operating voltage DC of line X1-3 UC 30 V
Maximum continuous operating voltage DC X1-9, X3-9, X5-9, X7-9 UC 70 V
Rated load current of line X1-2 IL 0.5 A
C2 Nominal discharge current (8/20) In 5 kA
C2 Voltage protection level X2-4 at +In Up < 56 V
C2 Voltage protection level X2-4 at -In Up > - 10 V
C3 Voltage protection level X2-4 at +1 kV/μs Up < 40 V
C3 Voltage protection level X2-4 at -1 kV/μs Up > - 1 V
B3 Voltage protection level X6-10, X8-10 at 100 V/μs Up < 550 V
C3 Voltage protection level X6-10, X8-10 at 1 kV/μs Up < 700 V
Serial resistance of line X1-2 R 1.6 Ω
Capacitance X2-4 at 0 V C 780 pF
Lightning protection zone LPZ 1-2, LPZ 2-3, LPZ3
Housing material Polyamid PA6, UL94 V-0
Degree of protection IP20
Operating temperature ϑ - 40 ÷ 70 °C
Clamp fastening range (solid conductor) 0.2 ÷ 4 mm2
Tightening moment 0,5
Installation On DIN rail 35 mm
Operating position Any
Remote signalling No
Modular design No