HDSP CIB
Article number: 56 057- Two-stage surge protection of connected CIB bus device.
- They are installed prior to the protected equipment and at the interface of LPZs 1 – 2 and higher.
- They increase the EMC level of the connected equipment against switching and atmospheric transients.
- Connecting the module allows to use the permanent maximum current load of the CIB bus, it is only necessary to check the permissible bus voltage drops within the whole installation by calculation.
- They provide cable shield protection by limiting pulse overvoltage through a built-in 90 V gas discharge tube.
Testing category according to IEC 61643-21:2000 and EN 61643-21:2001 | C2, C3, B3 | |
Number of pairs | 1 | |
Connector type | Screw terminals | |
Maximum continuous operating voltage DC of line X1-9, X3-9, X1-3 | UC | 36 V |
Maximum continuous operating voltage DC X7-9 | UC | 70 V |
Rated load current of line X1-2, X3-4 | IL | 1 A |
C2 Nominal discharge current (8/20) | In | 5 kA |
C2 Voltage protection level X2-10, X4-10 at In | Up | < 67 V |
C2 Voltage protection level X2-4 at In | Up | < 58 V |
C3 Voltage protection level X2-10, X4-10 at 1 kV/μs | Up | < 48 V |
C3 Voltage protection level X2-4 at 1 kV/μs | Up | < 46 V |
B3 Voltage protection level X8-10 at 100 V/μs | Up | < 550 V |
C3 Voltage protection level X8-10 at 1 kV/μs | Up | < 700 V |
Serial resistance of line X1-2, X3-4 | R | 0.8 Ω |
Capacitance X2-4 at 0 V | C | 550 pF |
Lightning protection zone | LPZ 1-2, LPZ 2-3, LPZ3 | |
Housing material | Polyamid PA6, UL94 V-0 | |
Degree of protection | IP20 | |
Operating temperature | ϑ | - 40 ÷ 70 °C |
Clamp fastening range (solid conductor) | 0.2 ÷ 4 mm2 | |
Tightening moment | 0,5 | |
Installation | On DIN rail 35 mm | |
Operating position | Any | |
Remote signalling | No | |
Pluggable version | No |