HDSP RS485/422

Article number: 56 056
  • Two-stage surge protection of connected RS485/422 bus device in Full-Duplex configuration.
  • They are installed prior to the protected equipment and at the interface of LPZs 1 – 2 and higher.
  • They increase the EMC level of the connected equipment against switching and atmospheric transients tested according to IEC 61000-4-2 (ESD level 4), IEC 61000-4-4 (EFT level 4) and IEC 61000-4-5 (shock pulse level X = 6 kV).
  • The connection of the module allows to use the operating range of bus drivers according to the TIA/EIA-485-A standard in the range of -7 V to +12 V (common-mode voltage range).
  • Connecting the module allows you to use the full 10 Mbps bus speed according to the TIA/EIA-485-A or TIA/EIA-422-B standard.
  • High-speed current protection of data line X1-2, X3-4, X5-6, X7-8 200 mA.
  • For extended protection of the common reference wire and bus shielding, use the additional mudule 1GDT/70.
Testing category according to IEC 61643-21:2000 and EN 61643-21:2001 C2, C3, B3
Number of pairs 2
Connector type Screw terminals
Maximum continuous operating voltage DC of data line X1-9, X3-9, X5-9, X7-9 UC - 7 ÷ 12 V
Rated load current of data line X1-2, X3-4, X5-6, X7-8 IL 0.2 A
Data link current protection at 25 °C Itrip 0.2 A
Max. response time for data link protection tblock 1 µs
C2 Nominal discharge current (8/20) In 5 kA
C2 Voltage protection level X2-10, X4-10, X6-10, X8-10 at +In Up 20 V
C2 Voltage protection level X2-10, X4-10, X6-10, X8-10 at -In Up - 12 V
C2 Voltage protection level X2-4, X6-8 at In Up 26 V
C3 Voltage protection level X2-10, X4-10, X6-10, X8-10 at +1 kV/μs Up 17 V
C3 Voltage protection level X2-10, X4-10, X6-10, X8-10 at -1 kV/μs Up - 10 V
C3 Voltage protection level X2-4, X6-8 at 1 kV/μs Up 25 V
Serial resistance of data line X1-2, X3-4, X5-6, X7-8 R 8.6 Ω
Capacitance X2-4, X6-8 at 0 V C 40 pF
Limiting transmission frequency S21 for Z0 = 120 Ω fC 50 MHz
Lightning protection zone LPZ 1-2, LPZ 2-3, LPZ3
Housing material Polyamid PA6, UL94 V-0
Degree of protection IP20
Operating temperature ϑ - 40 ÷ 70 °C
Clamp fastening range (solid conductor) 0.2 ÷ 4 mm2
Tightening moment 0,5
Installation On DIN rail 35 mm
Operating position Any
Remote signalling No
Pluggable version No
QUICK CONTACT
Quick contact
Ing. Aneta Sčebelová
 +420 494 942 314