Testing category according to IEC 61643-21:2000 and EN 61643-21:2001
|
|
C2, C3, B3
|
Number of pairs
|
|
2
|
Connector type
|
|
Screw terminals
|
Maximum continuous operating voltage DC of data line X1-9, X3-9, X5-9, X7-9
|
UC |
- 7 ÷ 12 V |
Rated load current of data line X1-2, X3-4, X5-6, X7-8
|
IL |
0.2 A
|
Data link current protection at 25 °C
|
Itrip |
0.2 A
|
Max. response time for data link protection
|
tblock |
1 µs
|
C2 Nominal discharge current (8/20)
|
In |
5 kA
|
C2 Voltage protection level X2-10, X4-10, X6-10, X8-10 at +In
|
Up |
20 V
|
C2 Voltage protection level X2-10, X4-10, X6-10, X8-10 at -In
|
Up |
- 12 V
|
C2 Voltage protection level X2-4, X6-8 at In
|
Up |
26 V
|
C3 Voltage protection level X2-10, X4-10, X6-10, X8-10 at +1 kV/μs
|
Up |
17 V
|
C3 Voltage protection level X2-10, X4-10, X6-10, X8-10 at -1 kV/μs
|
Up |
- 10 V
|
C3 Voltage protection level X2-4, X6-8 at 1 kV/μs
|
Up |
25 V
|
Serial resistance of data line X1-2, X3-4, X5-6, X7-8
|
R |
8.6 Ω
|
Capacitance X2-4, X6-8 at 0 V
|
C |
40 pF
|
Limiting transmission frequency S21 for Z0 = 120 Ω
|
fC |
50 MHz
|
Lightning protection zone
|
|
LPZ 1-2, LPZ 2-3, LPZ3
|
Housing material
|
|
Polyamid PA6, UL94 V-0
|
Degree of protection
|
|
IP20
|
Operating temperature
|
ϑ |
- 40 ÷ 70 °C |
Clamp fastening range (solid conductor)
|
|
0.2 ÷ 4 mm2 |
Tightening moment
|
|
0,5
|
Installation
|
|
On DIN rail 35 mm
|
Operating position
|
|
Any
|
Remote signalling
|
|
No |
Pluggable version
|
|
No |