HDSP RS485P
Article number: 56 055- Two-stage surge protection of connected RS485 bus device in Half-Duplex configuration with power line.
- They are installed prior to the protected equipment and at the interface of LPZs 1 – 2 and higher.
- They increase the EMC level of the connected equipment against switching and atmospheric transients tested according to IEC 61000-4-2 (ESD level 4), IEC 61000-4-4 (EFT level 4) and IEC 61000-4-5 (shock pulse level X = 6 kV).
- The connection of the module allows to use the operating range of bus drivers according to the TIA/EIA-485-A standard in the range of -7 V to +12 V (common-mode voltage range).
- Connecting the module allows you to use the full 10 Mbps bus speed according to the TIA/EIA-485-A.
- High-speed current protection of data line X1-2, X3-4 200 mA.
- Maximum current load of the power line 5 A.
pcs
Inquire
Testing category according to IEC 61643-21:2000 and EN 61643-21:2001 | C2, C3, B3 | |
Number of pairs | 1 | |
Connector type | Screw terminals | |
Maximum continuous operating voltage DC of data line X1-7, X3-7 | UC | - 7 ÷ 12 V |
Maximum continuous operating voltage DC of power line X5-7 | UC | 30 V |
Maximum continuous operating voltage DC X7-9 | UC | 70 V |
Rated load current of power line X5-6 | IL | 5 A |
Rated load current of data line X1-2, X3-4 | IL | 0.2 A |
Data link current protection at 25 °C | Itrip | 0.2 A |
Max. response time for data link protection | tblock | 1 µs |
C2 Nominal discharge current (8/20) | In | 5 kA |
C2 Voltage protection level X2-8, X4-8 at +In | Up | < 20 V |
C2 Voltage protection level X2-8, X4-8 at -In | Up | > - 12 V |
C2 Voltage protection level X2-4 at In | Up | < 26 V |
C2 Voltage protection level X6-8 at +In | Up | < 43 V |
C2 Voltage protection level X6-8 at -In | Up | > - 10 V |
C3 Voltage protection level X2-8, X4-8 at +1 kV/μs | Up | < 17 V |
C3 Voltage protection level X2-8, X4-8 at -1 kV/μs | Up | > - 10 V |
C3 Voltage protection level X2-4 at 1 kV/μs | Up | < 25 V |
C3 Voltage protection level X6-8 at +1 kV/μs | Up | < 40 V |
C3 Voltage protection level X6-8 at -1 kV/μs | Up | > - 1 V |
B3 Voltage protection level X8-10 at 100 V/μs | Up | < 550 V |
C3 Voltage protection level X8-10 at 1 kV/μs | Up | < 700 V |
Serial inductance of X5-6 power line | L | 2.2 μH |
Serial resistance of data line X1-2, X3-4 | R | 8.6 Ω |
Capacitance X2-4 at 0 V | C | 40 pF |
Limiting transmission frequency of data link S21 for Z0=120 Ω | fC | 50 MHz |
Lightning protection zone | LPZ1, LPZ2, LPZ3 | |
Housing material | Polyamid PA6, UL94 V-0 | |
Degree of protection | IP20 | |
Operating temperature | ϑ | - 40 ÷ 70 °C |
Clamp fastening range (solid conductor) | 0.2 ÷ 4 mm2 | |
Tightening moment | 0,5 | |
Installation | On DIN rail 35 mm | |
Operating position | Any | |
Remote signalling | No | |
Modular design | No |