Testing category according to IEC 61643-21:2000 and EN 61643-21:2001
|
|
C1, C2, C3
|
Connector type
|
|
Screw terminals
|
Rated operating DC voltage (Data line protection)
|
UN |
0 ÷ 6 V |
Maximum continuous operating voltage DC (Data line protection)
|
UC |
7.2 V
|
Rated load current (Data line protection)
|
IL |
0.1 A
|
Rated operating DC voltage (Power supply system protection)
|
UN |
0 ÷ 24 V |
Maximum continuous operating voltage DC (Power supply system protection)
|
UC |
28.6 V
|
Rated load current (Power supply system protection)
|
IL |
1.1 A
|
Hold-current of the resettable fuse at -40, 23, 70 °C
|
Ihold |
1790, 1100, 580 mA
|
Trip-current of the resettable fuse at -40, 23, 70 °C
|
Itrip |
3580, 2200, 1160 mA
|
C1 Nominal discharge current (8/20)
|
In |
1 kA
|
C1 Voltage protection level at In (line/G)
|
Up |
< 40 V
|
C1 Voltage protection level at In (line/line)
|
Up |
< 35 V
|
C2 Nominal discharge current (8/20)
|
In |
10 kA
|
C2 Voltage protection level at In (line/G)
|
Up |
< 60 V
|
C2 Voltage protection level at In (line/line)
|
Up |
< 40 V
|
C3 Voltage protection level at 1 kV/μs (line/G)
|
Up |
< 35 V
|
C3 Voltage protection level at 1 kV/μs (line/line)
|
Up |
< 35 V
|
Bandwidth
|
B |
0 ÷ 1 MHz |
Lightning protection zone
|
|
LPZ 1-2, LPZ 2-3, LPZ3
|
Housing material
|
|
Polyamid PA6, UL94 V-0
|
Degree of protection
|
|
IP20
|
Operating temperature
|
ϑ |
- 40 ÷ 70 °C |
Recommended cross-section of connected conductors
|
S |
0.25 ÷ 1.5 mm2 |
Clamp fastening range (solid conductor)
|
|
0.25 ÷ 4 mm2 |
Clamp fastening range (stranded conductor)
|
|
0.25 ÷ 2.5 mm2 |
Tightening moment
|
|
0,4
|
Installation
|
|
On DIN rail 35 mm
|
Modular width
|
|
1
|
Operating position
|
|
Any
|
Signalling at the device
|
|
None
|
Remote signalling
|
|
No |
Pluggable version
|
|
No |
Lifetime
|
|
> 100 000 h
|