HDT1/12B
Article number: 56 003- Designed for the protection of data and communication lines against longitudinal and transverse surge effects.
- Pluggable version.
- No interruption of communication bus when the module is removed.
- One pair or two pairs lines.
- Contains both 1st and 2nd stage of protection.
- The HDT*/*C range, in addition, contains a gas discharge tube between the PE and SH (shield) terminals for their galvanic isolation.
- Suitable for use in industrial applications, especially in low-voltage ESS, FDAS systems and also in measurement and control systems.
Testing category according to IEC 61643-21:2000 and EN 61643-21:2001 | C1, C2, C3, D1 | |
Number of pairs | 1 | |
Connector type | Screw terminals | |
Rated operating DC voltage | UN | 0 ÷ 12 V |
Maximum continuous operating voltage DC | UC | 14.4 V |
Rated load current | IL | 0.5 A |
C1 Voltage protection level at In (line/PE) | Up | < 250 V |
C1 Voltage protection level at In (line/line) | Up | < 50 V |
C1 Nominal discharge current (8/20) | In | 1 kA |
C2 Voltage protection level at In (line/PE) | Up | < 450 V |
C2 Voltage protection level at In (line/line) | Up | < 55 V |
C2 Nominal discharge current (8/20) | In | 15 kA |
C3 Voltage protection level at 1 kV/μs (line/PE) | Up | < 28 V |
C3 Voltage protection level at 1 kV/μs (line/line) | Up | < 18 V |
D1 Impulse discharge current (10/350) line/PE | Iimp | 2.5 kA |
D1 Total impulse discharge current (10/350) | ITotal | 5 kA |
Response time | tA | < 30 ns |
Data rate | 1 Mbit/s | |
Bandwidth | B | 0 ÷ 1 MHz |
Series impedance per line | 0.8 Ω | |
Parasitic capacitance | C | < 1.5 nF |
Lightning protection zone | LPZ 1-2, LPZ 2-3, LPZ3 | |
Housing material | Polyamid PA6, UL94 V-0 | |
Degree of protection | IP20 | |
Operating temperature | ϑ | - 40 ÷ 55 °C |
Clamp fastening range (solid conductor) | 0.2 ÷ 1.5 mm2 | |
Tightening moment | 0,5 | |
Installation | On DIN rail 35 mm | |
Modular width | 1 | |
Operating position | Any | |
Remote signalling | No | |
Pluggable version | Yes | |
Article number of spare module | 56 003/M | |
Lifetime | > 100 000 h |