HI16/15

Article number: 30 401
  • Ensure the energy coordination between the arresters type T1 and T2 or the arresters type T2 and T3, especially in the places where there is no adequate distance between the arresters.
  • If the energy coordination of surge protection is not observed, the excessive energy of passing impulse may cause a damage to the subsequent stage of the protective cascade.
  • If there is at least 5 m distance between two successive arrester types (in case of two successive arrester types in two different switchboards), it is possible to omit the decoupling element.
Rated operating AC voltage UN 500 V
Rated load current IL 16 A
Inductance ± 10 % L 15 μH
DC resistance R < 0.01 Ω
Maximal back-up fuse 16 A gL/gG
Thermal class of insulation A (105 °C)
Housing material Polyamid PA6, UL94 V-0
Degree of protection IP20
Operating temperature ϑ - 40 ÷ 70 °C
Humidity range RH 5 ÷ 95 %
Recommended cross-section of connected conductors S 6 mm2
Clamp fastening range (solid conductor) 1.5 ÷ 25 mm2
Clamp fastening range (stranded conductor) 1.5 ÷ 16 mm2
Tightening moment 3
Installation On DIN rail 35 mm
Modular width 1
Operating position Any
Product placement environment Internal
Remote signalling No
Modular design No