  • Ensure the energy coordination between the arresters type T1 and T2 or the arresters type T2 and T3, especially in the places where there is no adequate distance between the arresters.
  • If the energy coordination of surge protection is not observed, the excessive energy of passing impulse may cause a damage to the subsequent stage of the protective cascade.
  • If there is at least 15 meters distance between two successive protection stages (or 10 meters in the case of identical protective components, e.g., varistors), the separating inductor may be omitted. This applies to cases where two successive protection stages are located in separate distribution boards.
  • Separating inductors shall be installed on all live conductors including the N conductor.
Rated operating AC voltage UN 500 V
Rated load current IL 32 A
Inductance ± 10 % L 15 μH
DC resistance R < 0.01 Ω
Maximal back-up fuse 32 A gL/gG
Thermal class of insulation A (105 °C)
Housing material Polyamid PA6, UL94 V-0
Degree of protection IP20
Operating temperature ϑ - 40 ÷ 70 °C
Humidity range RH 5 ÷ 95 %
Recommended cross-section of connecting wires S 10 mm2
Clamp fastening range (solid conductor) 2.5 ÷ 35 mm2
Clamp fastening range (stranded conductor) 2.5 ÷ 25 mm2
Tightening torque 3
Installation On DIN rail 35 mm
Modular width 2
Operating position Any
Product placement environment Internal
Remote signalling No
Pluggable version No