HIG95-DELTA

Article number: 70 940
  • Insulation monitoring devices of the HIG95 series are devices for monitoring the insulation resistance of Medical IT systems.
  • In addition to the insulation resistance, the IMDs also evaluate the current and thermal load of the Medical IT system and thus meet the requirements for monitoring the medical, isolating transformer.
  • A whole range of monitoring panels is also available, making it easy to meet remote status signaling requirements. This is the MDS series.
  • The IMDs are equipped with a display for showing the currently measured values. The display together with the buttons is also used to set up the device.
Monitored IT power supply system type according to IEC 61557-8 AC, MED
Measuring range of insulation resistance RF 5 ÷ 10 000 kΩ
Adjustable range of critical insulation resistance Ran 50 ÷ 500 kΩ
Number of insulation resistance fault levels (Ran)
Rated voltage of monitored IT system (AC) Un 230 V
IMD power supply From measured IT system
Supply voltage range 85 ÷ 264 V
Visual signaling of thermal and current overload of the isolating transformer Yes
Monitoring of current overload of medical transformer Yes, using current transformers of the HIG-MT series
Monitoring of thermal overload of medical transformer Yes, temperature sensor is connected directly to the IMD
Supported temperature sensors 1x PT100, 2x PT100, 1x NC contact, 2x NC contact, 1x PTC thermistor, 2x PTC thermistor
Power consumption P 4 VA
Measuring voltage Um 12 V
Measuring current Im < 0.6 mA
Measuring input’s internal impedance Zi > 1 000 kΩ
Measuring accuracy ± 10 %
Electrical strength against internal circuits 3 000 V
Equipped with display Yes (OLED technology)
Supported module of remote monitoring panels (MDS) MDS-D, MDS-DELTA
Communication interface for user RS485 bus
Communication protocol ISOLGUARD
Housing material Polyamid PA6, UL94 V-0
Degree of protection of front panel IP40
Degree of protection except the front panel IP20
Operating temperature ϑ - 10 ÷ 60 °C
Protection class according to IEC 61140 II
Recommended cross-section of connecting wires S 1 mm2
Power conductor stripping length 7
Tightening torque 5
Installation On DIN rail 35 mm
Modular width 2
Width 36 mm
Height 90 mm
Depth 63.5 mm
Operating position Any
Operation type Permanent