HLA50-440/2+0 S
Article number: 10 958- Lightning impulse current arresters type T1 ensure the equipotential bonding and eliminate the effects of lightning current in single-phase and three-phase power supply systems.
- Products contain multiple non-exhausting spark gaps, thanks to which they are able to discharge the highest lightning impulse current.
- Suitable for objects with considerable levels of protection LPL I and LPL II, such as big industrial complexes and properties of particular importance – hospitals, banks, power plants.
- Installed as close as possible the overhead line enters the building i.e. the electric power substation, electrometer or the main distribution boards.
- If the product contains two PE (or PEN) terminals, it must not be used as a PE (PEN) bridge.
- LED indication specifies a version with LED fault signalisation.
- S indication specifies a version with remote monitoring and LED fault signalisation.
Impulse discharge current for class I test (10/350) | Iimp | 50 kA |
Test class according to EN 61643-11:2012 (IEC 61643-11:2011) | T1 | |
System | TN-S | |
Number of poles | 2 | |
Rated operating AC voltage | UN | 400 V |
Maximum continuous operating voltage AC | UC | 440 V |
Charge | Q | 25 As |
Specific energy for class I test | W/R | 625 kJ/Ω |
Total discharge current (10/350) L+N->PE | ITotal | 100 kA |
Nominal discharge current for class II test (8/20) | In | 50 kA |
Voltage protection level at Iimp | Up | < 2.5 kV |
Temporary overvoltage test (TOV) for tT = 5 s | UT | 581 V |
Temporary overvoltage test (TOV) for tT = 120 min | UT | 762 V |
Response time | tA | < 100 ns |
Maximal back-up fuse | 500 A gL/gG | |
Short-circuit current rating at maximum back-up fuse | ISCCR | 3 kArms |
Follow current interrupt rating | Ifi | 3 kArms |
Lightning protection zone | LPZ 0-1, LPZ 1-2 | |
Housing material | Polyamid PA6, UL94 V-0 | |
Degree of protection | IP20 | |
Operating temperature | ϑ | - 40 ÷ 70 °C |
Humidity range | RH | 5 ÷ 95 % |
Minimum cross-section of connected Cu conductors accord. to HD 60364-5-53:2022 (doesn't apply to „V“ connection) for T1 | S |
6 mm² (L, N) 16 mm² (PE, PEN) |
Clamp fastening range (solid conductor) | 2.5 ÷ 25 mm2 | |
Clamp fastening range (stranded conductor) | 2.5 ÷ 16 mm2 | |
Tightening moment | 4 | |
Installation | On DIN rail 35 mm | |
Modular width | 4 | |
Operating position | Any | |
Product placement environment | Internal | |
Signalling at the device | Optic | |
Importance of local signaling |
OK – green light on FAULT – red light on |
|
Remote signalling | Yes | |
Potential free signal contact (S) (recommended cross-section of remote monitoring max. 1 mm2) | AC: 250 V / 1.5 A, AC: 250 V / 0.5 A, DC: 250 V / 0.1 A, DC: 30 V / 0,03 A | |
Pluggable version | No | |
Lifetime | > 100 000 h |