HLSA12,5-275 Module

Article number: 16 086
  • Removable modules for lightning impulse current and surge arresters type T1+T2+T3.
  • Ensure the equipotential bonding, eliminate the effects of lightning current and reduce switching, induced and residual overvoltage in single-phase and three-phase power supply systems entering the building.
  • Installed at the boundaries of LPZ 0 – LPZ 1 and higher zones, closest to where overhead line enters the building i.e. in the main distribution boards.
  • The products consist of varistors with big discharge ability.
Impulse discharge current for class I test (10/350) Iimp 12.5 kA
Test class according to EN 61643-11:2012 (IEC 61643-11:2011) T1, T2, T3
CB test certificate number according to the IEC 61643-11:2011 from the CTI – VIENNA laboratory AT 5110
Maximum continuous operating voltage AC UC 275 V
Nominal discharge current for class II test (8/20) In 25 kA
Open circuit voltage of the combination wave generator UOC 6 kV
Voltage protection level at In Up < 1.25 kV
Spare module for 16080, 16090, 16081, 16091, 16082, 16092, 16083, 16093, 16084, 16094, 16085, 16095