HLSA12,5 PV 1500/2

Article number: 10 479
  • Lightning impulse current and surge arresters type T1+T2 intended for photovoltaic systems (PV) at U or Y connection.
  • The advantage of the Y connection versus the U connection is the resistance to the earth connection of the working conductors and zero residual (leakage) current through the PE conductor.
  • Particular varistor sectors, connected between the terminals L+, L- and PE are equipped with internal disconnectors, which are activated when the varistors fail (overheat).
  • These devices are necessary to be used with the back-up fuse with external disconnector, which is intended for PV applications.
  • They are installed on the DC side in PV applications with external LPS, where a sufficient distance "s" is not observed.
  • Suitable for level LPL I or II.
  • Ensure the equipotential bonding of plus and minus busbars of PV systems and the elimination of transient overvoltage resulting from the atmospheric discharges (including direct lightning strike to the PV system) or switching processes.
  • S indication specifies a version with remote monitoring.
Impulse discharge current for class I test (10/350) Iimp 12.5 kA
Test class according to EN 61643-11:2012 and EN 61643-31:2019 T1, T2
System DC
PV system type Ungrounded
SPD connection type U
Maximum continuous operating voltage (+/-) UCPV 1 500 V DC
Maximum continuous operating voltage (±/PE) UCPV 750 V DC
Max. voltage of PV generator UOCSTC ≤ UCPV / 1.2 UOCSTC 1 250 V
Short-circuit current rating ISCPV 10 kA
Charge Q 6.25 As
Specific energy for class I test W/R 39 kJ/Ω
Total discharge current (10/350) ±->PE ITotal 25 kA
Total discharge current (8/20) ±->PE ITotal 40 kA
Maximum discharge current (8/20) Imax 40 kA
Nominal discharge current for class II test (8/20) In 20 kA
Voltage protection level at In (+/-) Up < 4.8 kV
Voltage protection level at In (±/PE) Up < 2.4 kV
Response time (+/-) tA < 25 ns
Response time (±/PE) tA < 25 ns
Housing material Polyamid PA6, UL94 V-0
Degree of protection IP20
Operating temperature ϑ - 40 ÷ 70 °C
Humidity range RH 5 ÷ 95 %
Minimum cross-section of connected Cu conductors according to IEC 61643-32:2017 (doesn't apply to „V“ connection) for T1 S 6 mm² (L+, L-)
16 mm² (PE)
Minimum cross-section of connected Cu conductors according to IEC 61643-32:2017 (doesn't apply to „V“ connection) for T2 S 2.5 mm² (L+, L-)
6 mm² (PE)
Clamp fastening range (solid conductor) 1.5 ÷ 25 mm2
Clamp fastening range (stranded conductor) 1.5 ÷ 16 mm2
Tightening moment 3
Installation On DIN rail 35 mm
Modular width 4
Operating position Any
Product placement environment Internal
Signalling at the device Optic
Importance of local signaling OK – clear target
FAULT – red target
Remote signalling No
Pluggable version No
Lifetime > 100 000 h