HLSA25-275/4+0
Article number: 10 455- Lightning impulse current and surge arresters type T1+T2+T3.
- The products consist of varistors with big discharge ability.
- HLSA25 in configurations 1+1, 3+1 and HLSA25G are additionally combined with a gas discharge tube which ensures zero leakage current through the PE conductor.
- Suitable for objects with considerable levels of protection LPL I and LPL II.
- Installed at the boundaries of LPZ 0 – LPZ 1 and higher zones, closest to where overhead line enters the building i.e. in the main distribution boards.
- In case of the installation of a type T1+T2+T3 in the main switchboard, it is also necessary to install type T2 and T3 in any additional distribution boards in the electrical installation.
- If the product contains two PE (or PEN) terminals, it must not be used as a PE (PEN) bridge.
- S indication specifies a version with remote monitoring.
Impulse discharge current for class I test (10/350) | Iimp | 25 kA |
Test class according to EN 61643-11:2012 (IEC 61643-11:2011) | T1, T2, T3 | |
System | TN-S | |
Number of poles | 4 | |
Rated operating AC voltage | UN | 230 V |
Maximum continuous operating voltage AC | UC | 275 V |
Rated load current for „V“ connection | IL | 125 A |
Maximum discharge current (8/20) | Imax | 50 kA |
Charge | Q | 12.5 As |
Specific energy for class I test | W/R | 156 kJ/Ω |
Total discharge current (10/350) L1+L2+L3+N->PE | ITotal | 100 kA |
Total discharge current (8/20) L1+L2+L3+N->PE | ITotal | 200 kA |
Nominal discharge current for class II test (8/20) | In | 25 kA |
Open circuit voltage of the combination wave generator | UOC | 6 kV |
Voltage protection level at In | Up | < 1.2 kV |
Temporary overvoltage test (TOV) for tT = 5 s | UT | 337 V |
Temporary overvoltage test (TOV) for tT = 120 min | UT | 440 V |
Response time | tA | < 25 ns |
Maximal back-up fuse | 250 A gL/gG | |
Maximal back-up fuse („V“ connection) | 125 A gL/gG | |
Residual current | IPE | ≤ 300 µA |
Short-circuit current rating at maximum back-up fuse | ISCCR | 80 kArms |
Lightning protection zone | LPZ 0-1, LPZ 1-2, LPZ 2-3, LPZ3 | |
Housing material | Polyamid PA6, UL94 V-0 | |
Degree of protection | IP20 | |
Operating temperature | ϑ | - 40 ÷ 70 °C |
Humidity range | RH | 5 ÷ 95 % |
Minimum cross-section of connected Cu conductors accord. to HD 60364-5-53:2022 (doesn't apply to „V“ connection) for T1 | S |
6 mm² (L, N) 16 mm² (PE, PEN) |
Minimum cross-section of connected Cu conductors accord. to HD 60364-5-53:2022 (doesn't apply to „V“ connection) for T2 | S |
2.5 mm² (L, N) 6 mm² (PE, PEN) |
Clamp fastening range (solid conductor) | 2.5 ÷ 35 mm2 | |
Clamp fastening range (stranded conductor) | 2.5 ÷ 25 mm2 | |
Tightening moment | 3 | |
Installation | On DIN rail 35 mm | |
Modular width | 8 | |
Operating position | Any | |
Product placement environment | Internal | |
Signalling at the device | Optic | |
Importance of local signaling |
OK – clear target FAULT – red target |
|
Remote signalling | No | |
Pluggable version | No | |
Lifetime | > 100 000 h |