HLSA6,5 PV 800/2 Module

Article number: 16 377
  • Removable modules for lightning impulse current and surge arresters type T1+T2 intended for photovoltaic systems (PV).
  • They are installed on the DC side in PV applications with external LPS, where a sufficient distance "s" is not observed.
  • Suitable for level LPL III or IV.
  • Ensure the equipotential bonding of plus and minus busbars of PV systems and the elimination of transient overvoltage resulting from the atmospheric discharges (including direct lightning strike to the PV system) or switching processes.
Impulse discharge current for class I test (10/350) Iimp 6.5 kA
Test class according to EN 61643-11:2012 and EN 61643-31:2019 T1, T2
Maximum continuous operating voltage (+/-) UCPV 800 V DC
Maximum continuous operating voltage (±/PE) UCPV 400 V DC
Nominal discharge current for class II test (8/20) In 20 kA
Voltage protection level at In (+/-) Up < 3.4 kV
Voltage protection level at In (±/PE) Up < 1.7 kV
Spare module for 16 368, 16 369