HSAA-2 NPE LED S

Article number: 32 010
  • Surge arresters type T3 specially adapted for the protection of LED lights.
  • Intended for mounting directly to the lights.
  • Installed at the boundaries of LPZ 2 – LPZ 3, as close as possible to the protected device (no further than 5 m).
  • A lightning and surge arrester T1 and T2 from HAKEL company must be installed in front of the HSAA-2 NPE LED S.
  • S indication specifies a version with remote monitoring.
Test class according to EN 61643-11:2012 (IEC 61643-11:2011) T3
Number of poles
Rated operating AC voltage UN 230 V
Maximum continuous operating voltage AC UC 320 V
Rated load current IL 10 A
Open circuit voltage of the combination wave generator UOC 6 kV
Voltage protection level at UOC (L/N) Up < 1.3 kV
Voltage protection level at UOC (L/PE, N/PE) Up < 1.5 kV
Nominal discharge current for class II test (8/20) In 3 kA
Maximum discharge current (8/20) Imax 8 kA
Temporary overvoltage test (TOV) for tT = 5 s (L/N) UT 337 V
Temporary overvoltage test (TOV) for tT = 120 min (L/N) UT 440 V
Temporary overvoltage test (TOV) for tT = 0.2 s (N/PE) UT 1 200 V
Response time (L/N) tA < 25 ns
Response time (L/PE, N/PE) tA < 100 ns
Maximal back-up fuse 10 A gL/gG
Residual current IPE ≤ 5 µA
Lightning protection zone LPZ 2-3, LPZ3
Housing material Polyamid PA6, UL94 V-0
Degree of protection IP20
Operating temperature ϑ - 40 ÷ 70 °C
Humidity range RH 5 ÷ 95 %
Recommended cross-section of connected conductors S 1.5 mm2
Installation In the installation box, Built-in installation, Wiring cable duct
Product placement environment Internal
Signalling at the device None
Remote signalling Yes
Importance of remote signalling Potential opening contact (voltage loss)
Includes EMI / EMC filter No
Pluggable version No
Lifetime > 100 000 h