HSAA-2 NPE LED S
Article number: 32 010- Surge arresters type T3 specially adapted for the protection of LED lights.
- Intended for mounting directly to the lights.
- Installed at the boundaries of LPZ 2 – LPZ 3, as close as possible to the protected device (no further than 5 m).
- A lightning and surge arrester T1 and T2 from HAKEL company must be installed in front of the HSAA-2 NPE LED S.
- S indication specifies a version with remote monitoring.
pcs
Inquire
Test class according to EN 61643-11:2012 (IEC 61643-11:2011) | T3 | |
Number of poles | 2 | |
Rated operating AC voltage | UN | 230 V |
Maximum continuous operating voltage AC | UC | 320 V |
Rated load current | IL | 10 A |
Open circuit voltage of the combination wave generator | UOC | 6 kV |
Voltage protection level at UOC (L/N) | Up | < 1.3 kV |
Voltage protection level at UOC (L/PE, N/PE) | Up | < 1.5 kV |
Nominal discharge current for class II test (8/20) | In | 3 kA |
Maximum discharge current (8/20) | Imax | 8 kA |
Temporary overvoltage test (TOV) for tT = 5 s (L/N) | UT | 337 V |
Temporary overvoltage test (TOV) for tT = 120 min (L/N) | UT | 440 V |
Temporary overvoltage test (TOV) for tT = 0.2 s (N/PE) | UT | 1 200 V |
Response time (L/N) | tA | < 25 ns |
Response time (L/PE, N/PE) | tA | < 100 ns |
Maximal back-up fuse | 10 A gL/gG | |
Residual current | IPE | ≤ 5 µA |
Lightning protection zone | LPZ2, LPZ3 | |
Housing material | Polyamid PA6, UL94 V-0 | |
Degree of protection | IP20 | |
Operating temperature | ϑ | - 40 ÷ 70 °C |
Humidity range | RH | 5 ÷ 95 % |
Recommended cross-section of connected conductors | S | 1.5 mm2 |
Installation | In the installation box, Built-in installation, Wiring cable duct | |
Product placement environment | Internal | |
Signalling at the device | None | |
Remote signalling | Yes | |
Importance of remote signalling | Potential opening contact (voltage loss) | |
Includes EMI / EMC filter | No | |
Modular design | No | |
Lifetime | > 100 000 h |