HSAD-S M S

Article number: 30 370
  • Surge arresters type T3 for serial (HSAD-S M S) or parallel (HSAD-P M S) connection.
  • Intended for protection of one-phase electronic appliances against the effects of switching, induced and residual overvoltage generated in LV power supply systems.
  • Installed at the boundaries of LPZ 2 – LPZ 3, as close to the device to be protected as possible (no further than 5 m).
  • In front of HSAD-S M S/HSAD-P M S must be installed a lightning current and surge arrester T1 and T2 from HAKEL company.
  • Compact dimensions with a constructional modular width of 1 TE.
  • A type of construction with a removable module.
  • S indication specifies a version with remote monitoring.
Test class according to EN 61643-11:2012 (IEC 61643-11:2011) T3
System TN-C-S, TN-S
Number of poles
Rated operating AC voltage UN 230 V
Maximum continuous operating voltage AC UC 275 V
Rated load current IL 10 A
Open circuit voltage of the combination wave generator (L/N, L/PE) UOC 6 kV
Open circuit voltage of the combination wave generator (N/PE) UOC 10 kV
Voltage protection level at UOC (L/N) Up < 1 kV
Voltage protection level at UOC (L/PE, N/PE) Up < 1.5 kV
Nominal discharge current for class II test (8/20) L/N, L/PE In 3 kA
Nominal discharge current for class II test (8/20) N/PE In 5 kA
Total discharge current (8/20) L+N->PE ITotal 6 kA
Temporary overvoltage test (TOV) for tT = 5 s (L/N) UT 337 V
Temporary overvoltage test (TOV) for tT = 120 min (L/N) UT 440 V
Temporary overvoltage test (TOV) for tT = 0.2 s (N/PE) UT 1 200 V
Response time (L/N) tA < 25 ns
Response time (L/PE, N/PE) tA < 100 ns
Maximal back-up fuse 10 A gL/gG
Residual current IPE ≤ 5 µA
Lightning protection zone LPZ 2-3, LPZ3
Housing material Polyamid PA6, UL94 V-0
Degree of protection IP20
Operating temperature ϑ - 40 ÷ 55 °C
Humidity range RH 5 ÷ 95 %
Recommended cross-section of connected conductors S 1.5 mm2
Clamp fastening range (solid conductor) 0.2 ÷ 4 mm2
Clamp fastening range (stranded conductor) 0.2 ÷ 2.5 mm2
Tightening moment 0,5
Installation On DIN rail 35 mm
Modular width 1
Operating position Any
Product placement environment Internal
Signalling at the device Optic
Importance of local signaling OK – green light on
FAULT – green light off
Remote signalling Yes
Potential free signal contact (S) (recommended cross-section of remote monitoring max. 1 mm2) AC: 250 V / 1.5 A, DC: 250 V / 0.1 A
Includes EMI / EMC filter No
Modular design Yes
Article number of spare module 30 390
Lifetime > 100 000 h