HSAF10/6VDC S

Article number: 30 267
  • Two-port surge arresters type T3 with high-frequency filters for serial connection.
  • Intended for protection of electronic appliances against the effects of switching, induced and residual overvoltage in DC power supply systems.
  • Contain an improved thermal fuse, which ensures timely disconnection of HSAF*VDC S from the power grid during the MOV‘s overheating and thus prevents damage to the HSAF*VDC S.
  • Installed at the boundaries of LPZ 2 – LPZ 3, as close to the device to be protected as possible (no further than 5 m).
  • In front of HSAF*VDC S must be installed a lightning current and surge arrester T1 and T2 from HAKEL company.
  • S indication specifies a version with remote monitoring.
Test class according to EN 61643-11:2012 (IEC 61643-11:2011) T3
System DC
Rated operating DC voltage UN 6 V
Maximum continuous operating voltage DC UC 7.2 V
Rated load current IL 10 A
Open circuit voltage of the combination wave generator (+/-, ±/PE) UOC 4 kV
Voltage protection level at UOC (+/-) Up < 0.35 kV
Voltage protection level at UOC (±/PE) Up < 0.3 kV
Nominal discharge current for class II test (8/20) +/-, ±/PE In 2 kA
Total discharge current (8/20) ±->PE ITotal 4 kA
Asymmetrical attenuation of filter at f = 4 MHz > 80 dB
Asymmetrical attenuation of filter at f = 0.15 ÷ 30 MHz > 35 dB
Response time (+/-) tA < 25 ns
Response time (±/PE) tA < 100 ns
Power dissipation Pz < 2.2 W
Maximal back-up fuse 10 A gL/gG
Residual current IPE ≤ 1 800 µA
Short-circuit current rating at maximum back-up fuse ISCCR 6 kArms
Lightning protection zone LPZ 2-3, LPZ3
Housing material Polyamid PA6, UL94 V-0
Degree of protection IP20
Operating temperature ϑ - 40 ÷ 55 °C
Humidity range RH 5 ÷ 95 %
Recommended cross-section of connected conductors S 1.5 mm2
Clamp fastening range (solid conductor) 0.2 ÷ 6 mm2
Clamp fastening range (stranded conductor) 0.2 ÷ 4 mm2
Tightening moment 1,2
Installation On DIN rail 35 mm
Modular width 4
Operating position Any
Product placement environment Internal
Signalling at the device Optic
Importance of local signaling OK – red light off
FAULT – red light on
Remote signalling Yes
Potential free signal contact (S) (recommended cross-section of remote monitoring max. 1 mm2) AC: 250 V / 1.5 A, DC: 250 V / 0.1 A
Includes EMI / EMC filter Yes
Pluggable version No
Lifetime > 100 000 h