HSAF125 S
Article number: 30 176- Two-port surge arresters type T3 with high-frequency filters for serial connection.
- Intended for protection of electronic appliances against the effects of switching, induced and residual overvoltage in LV power supply systems.
- Contains an improved thermal fuse, which ensures timely disconnection of HSAF* S and HSAF3*S from the power grid during the MOV‘s overheating and thus prevents damage to the HSAF* S and HSAF3*S.
- Installed at the boundaries of LPZ 2 – LPZ 3, as close to the device to be protected as possible (no further than 5 m).
- In front of HSAF* S and HSAF3*S must be installed a lightning current and surge arrester T1 and T2 from HAKEL company.
- Mounted on the main board of a switchboard using four screws.
- S indication specifies a version with remote monitoring.
Test class according to EN 61643-11:2012 (IEC 61643-11:2011) | T3 | |
System | TN-C-S, TN-S | |
Number of poles | 2 | |
Rated operating AC voltage | UN | 230 V |
Maximum continuous operating voltage AC | UC | 275 V |
Rated load current | IL | 125 A |
Open circuit voltage of the combination wave generator (L/N, L/PE) | UOC | 6 kV |
Open circuit voltage of the combination wave generator (N/PE) | UOC | 10 kV |
Voltage protection level at UOC (L/N) | Up | < 0.85 kV |
Voltage protection level at UOC (L/PE) | Up | < 1.5 kV |
Voltage protection level at UOC (N/PE) | Up | < 1.2 kV |
Nominal discharge current for class II test (8/20) L/N, L/PE | In | 3 kA |
Nominal discharge current for class II test (8/20) N/PE | In | 5 kA |
Total discharge current (8/20) L+N->PE | ITotal | 6 kA |
Asymmetrical attenuation of filter at f = 4 MHz | > 80 dB | |
Asymmetrical attenuation of filter at f = 0.15 ÷ 30 MHz | > 35 dB | |
Temporary overvoltage test (TOV) for tT = 5 s (L/N) | UT | 337 V |
Temporary overvoltage test (TOV) for tT = 120 min (L/N) | UT | 440 V |
Temporary overvoltage test (TOV) for tT = 0.2 s (N/PE) | UT | 1 200 V |
Response time (L/N) | tA | < 25 ns |
Response time (L/PE, N/PE) | tA | < 100 ns |
Power dissipation | Pz | < 20 W |
Maximal back-up fuse | 125 A gL/gG | |
Residual current | IPE | ≤ 5 µA |
Lightning protection zone | LPZ 2-3, LPZ3 | |
Housing material | Steel plate 1 mm | |
Degree of protection | IP20 | |
Operating temperature | ϑ | - 40 ÷ 55 °C |
Humidity range | RH | 5 ÷ 95 % |
Recommended cross-section of connected conductors | S | 35 mm2 |
Clamp fastening range (solid conductor) | 1.5 ÷ 50 mm2 | |
Clamp fastening range (stranded conductor) | 1.5 ÷ 35 mm2 | |
Tightening moment | 10 | |
Installation | Using the M4 screws on the chassis | |
Operating position | Any | |
Product placement environment | Internal | |
Signalling at the device | Optic | |
Importance of local signaling |
OK – red light off FAULT – red light on |
|
Remote signalling | Yes | |
Potential free signal contact (S) (recommended cross-section of remote monitoring max. 1 mm2) | AC: 250 V / 1.5 A, DC: 250 V / 0.1 A | |
Includes EMI / EMC filter | Yes | |
Pluggable version | No | |
Lifetime | > 100 000 h |