HSAF16 S IT

Article number: 30 501
  • Surge arresters type T3 with high-frequency filters for serial connection.
  • Intended for protection of electronic appliances against the effects of switching, induced and residual overvoltage in insulated power supply systems.
  • Contain an improved thermal fuse, which ensures timely disconnection of HSAF* S from the power grid during the MOV‘s overheating and thus prevents damage to the HSAF* S.
  • Installed at the boundaries of LPZ 2 – LPZ 3, as close to the device to be protected as possible (no further than 5 m).
  • In front of HSAF* S must be installed a lightning current and surge arrester T1 and T2 from HAKEL company.
  • S indication specifies a version with remote monitoring.
Test class according to EN 61643-11:2012 (IEC 61643-11:2011) T3
System IT
Number of poles
Rated operating AC voltage UN 230 V
Maximum continuous operating voltage AC UC 275 V
Rated load current IL 16 A
Open circuit voltage of the combination wave generator UOC 6 kV
Voltage protection level at UOC (L1/L2) Up < 1.4 kV
Voltage protection level at UOC (L1/PE, L2/PE) Up < 0.9 kV
Nominal discharge current for class II test (8/20) In 3 kA
Total discharge current (8/20) L1+L2->PE ITotal 6 kA
Asymmetrical attenuation of filter at f = 4 MHz > 80 dB
Asymmetrical attenuation of filter at f = 0.15 ÷ 30 MHz > 35 dB
Temporary overvoltage test (TOV) for tT = 5 s (L1/L2) UT 337 V
Temporary overvoltage test (TOV) for tT = 0.2 s (L1/PE, L2/PE) UT 1 455 V
Response time (L1/L2) tA < 25 ns
Response time (L1/PE, L2/PE) tA < 100 ns
Power dissipation Pz < 3.5 W
Maximal back-up fuse 16 A gL/gG
Lightning protection zone LPZ 2-3, LPZ3
Housing material Polyamid PA6, UL94 V-0
Degree of protection IP20
Operating temperature ϑ - 40 ÷ 55 °C
Recommended cross-section of connected conductors S 2.5 mm2
Clamp fastening range (solid conductor) 0.2 ÷ 6 mm2
Clamp fastening range (stranded conductor) 0.2 ÷ 4 mm2
Tightening moment 1,2
Installation On DIN rail 35 mm
Modular width 4
Operating position Any
Signalling at the device Optic
Importance of local signaling OK – red light off
FAULT – red light on
Remote signalling Yes
Potential free signal contact (S) (recommended cross-section of remote monitoring max. 1 mm2) AC: 250 V / 1.5 A, DC: 250 V / 0.1 A
Includes EMI / EMC filter Yes
Modular design No
Lifetime > 100 000 h