HSAF3/125 S

Article number: 30 194
  • Two-port surge arresters type T3 with high-frequency filters for serial connection.
  • Intended for protection of electronic appliances against the effects of switching, induced and residual overvoltage in LV power supply systems.
  • Contains an improved thermal fuse, which ensures timely disconnection of HSAF* S and HSAF3*S from the power grid during the MOV‘s overheating and thus prevents damage to the HSAF* S and HSAF3*S.
  • Installed at the boundaries of LPZ 2 – LPZ 3, as close to the device to be protected as possible (no further than 5 m).
  • In front of HSAF* S and HSAF3*S must be installed a lightning current and surge arrester T1 and T2 from HAKEL company.
  • Mounted on the main board of a switchboard using four screws.
  • S indication specifies a version with remote monitoring.
Test class according to EN 61643-11:2012 (IEC 61643-11:2011) T3
System TN-C-S, TN-S
Number of poles
Rated operating AC voltage UN 230 V
Maximum continuous operating voltage AC UC 275 V
Rated load current IL 125 A
Open circuit voltage of the combination wave generator (L/N, L/PE) UOC 6 kV
Open circuit voltage of the combination wave generator (N/PE) UOC 10 kV
Voltage protection level at UOC (L/N) Up < 0.85 kV
Voltage protection level at UOC (L/PE) Up < 1.5 kV
Voltage protection level at UOC (N/PE) Up < 1.2 kV
Nominal discharge current for class II test (8/20) L/N, L/PE In 3 kA
Nominal discharge current for class II test (8/20) N/PE In 5 kA
Total discharge current (8/20) L1+L2+L3+N->PE ITotal 12 kA
Asymmetrical attenuation of filter at f = 4 MHz > 80 dB
Asymmetrical attenuation of filter at f = 0.15 ÷ 30 MHz > 35 dB
Temporary overvoltage test (TOV) for tT = 5 s (L/N) UT 337 V
Temporary overvoltage test (TOV) for tT = 120 min (L/N) UT 440 V
Temporary overvoltage test (TOV) for tT = 0.2 s (N/PE) UT 1 200 V
Response time (L/N) tA < 25 ns
Response time (L/PE, N/PE) tA < 100 ns
Power dissipation Pz < 20 W
Maximal back-up fuse 125 A gL/gG
Residual current IPE ≤ 5 µA
Lightning protection zone LPZ 2-3, LPZ3
Housing material Steel plate 1 mm
Degree of protection IP20
Operating temperature ϑ - 40 ÷ 55 °C
Humidity range RH 5 ÷ 95 %
Recommended cross-section of connected conductors S 35 mm2
Power conductor stripping length 18
Remote monitoring conductor stripping length 7
Clamp fastening range (solid conductor) 1.5 ÷ 50 mm2
Clamp fastening range (stranded conductor) 1.5 ÷ 35 mm2
Remote monitoring contact terminal clamp range 0.5 ÷ 1.5 mm2
Tightening moment 10
Tightening torque for remote signaling 0,2
Installation Using the M4 screws on the chassis
Width 290 mm
Height 180 mm
Depth 75 mm
Operating position Any
Product placement environment Internal
Signalling at the device Optic
Importance of local signaling OK – red light off
FAULT – red light on
Remote signalling Yes
Potential free signal contact (S) (recommended cross-section of remote monitoring max. 1 mm2) AC: 250 V / 1.5 A, DC: 250 V / 0.1 A
Includes EMI / EMC filter Yes
Pluggable version No
Lifetime > 100 000 h