HT-CCTV-6 Xseries
Article number: 57 001- Surge protection devices of coaxial lines 50 Ω or 75 Ω with connection via BNC connector.
- Designed to protect the equipment of older video transmission systems from the effects of induced overvoltage.
- They are installed as close as possible to the protected equipment, such as cameras or video signal concentrators.
Testing category according to IEC 61643-21:2000 and EN 61643-21:2001 | C1, C2, C3 | |
Number of pairs | 1 | |
Connector type | BNC | |
Rated operating DC voltage | UN | 0 ÷ 6 V |
Maximum continuous operating voltage DC | UC | 7.2 V |
Rated load current | IL | 0.3 A |
Maximum discharge current (8/20) | Imax | 5 kA |
C2 Nominal discharge current (8/20) | In | 1 kA |
C2 Voltage protection level at In | Up | < 22 V |
C3 Voltage protection level at 1 kV/μs | Up | < 10 V |
Response time | tA | < 30 ns |
Data rate | 10 Mbit/s | |
Bandwidth | B | 0 ÷ 10 MHz |
Series impedance per line | 2.2 Ω | |
Parasitic capacitance | C | < 0.03 nF |
Lightning protection zone | LPZ 1-2, LPZ 2-3, LPZ3 | |
Housing material | AlMgSi (EN AW 6060) | |
Degree of protection | IP20 | |
Operating temperature | ϑ | - 40 ÷ 70 °C |
Installation | On DIN rail 35 mm | |
Operating position | Any | |
Signalling at the device | None | |
Remote signalling | No |