Testing category according to IEC 61643-21:2000 and EN 61643-21:2001
|
|
C1, C2, C3, D1
|
Number of pairs
|
|
1
|
Connector type
|
|
Two-pole screw plug-in terminal block
|
Rated operating DC voltage
|
UN |
0 ÷ 24 V |
Maximum continuous operating voltage DC
|
UC |
28.8 V
|
Rated load current
|
IL |
0.1 A
|
Maximum discharge current (8/20)
|
Imax |
10 kA
|
C2 Nominal discharge current (8/20)
|
In |
1 kA
|
C2 Voltage protection level at In
|
Up |
< 64 V
|
C3 Voltage protection level at 1 kV/μs
|
Up |
< 34 V
|
D1 Impulse discharge current (10/350) line/PE
|
Iimp |
2.5 kA
|
D1 Total impulse discharge current (10/350)
|
ITotal |
5 kA
|
Response time
|
tA |
< 30 ns
|
Data rate
|
|
1 Mbit/s
|
Bandwidth
|
B |
0 ÷ 1 MHz |
Series impedance per line
|
|
2.2 Ω
|
Parasitic capacitance
|
C |
< 1.5 nF
|
Lightning protection zone
|
|
LPZ 0-1, LPZ 1-2, LPZ 2-3, LPZ3
|
Housing material
|
|
AlMgSi (EN AW 6060)
|
Degree of protection
|
|
IP20
|
Operating temperature
|
ϑ |
- 40 ÷ 70 °C |
Clamp fastening range (solid conductor)
|
|
0.2 ÷ 2.5 mm2 |
Tightening moment
|
|
0,5
|
Installation
|
|
On DIN rail 35 mm
|
Operating position
|
|
Any
|
Remote signalling
|
|
No |