HT-D 1/24 Xseries
Article number: 57 007- Designed for the protection of data and communication lines against longitudinal and transverse surge effects.
- Contains both 1st and 2nd stage of protection.
- Suitable for use in industrial applications, especially in low-voltage ESS, FDAS systems and also in measurement and control systems.
Testing category according to IEC 61643-21:2000 and EN 61643-21:2001 | C1, C2, C3, D1 | |
Number of pairs | 1 | |
Connector type | Two-pole screw plug-in terminal block | |
Rated operating DC voltage | UN | 0 ÷ 24 V |
Maximum continuous operating voltage DC | UC | 28.8 V |
Rated load current | IL | 0.1 A |
Maximum discharge current (8/20) | Imax | 10 kA |
C2 Nominal discharge current (8/20) | In | 1 kA |
C2 Voltage protection level at In | Up | < 64 V |
C3 Voltage protection level at 1 kV/μs | Up | < 34 V |
D1 Impulse discharge current (10/350) line/PE | Iimp | 2.5 kA |
D1 Total impulse discharge current (10/350) | ITotal | 5 kA |
Response time | tA | < 30 ns |
Data rate | 1 Mbit/s | |
Bandwidth | B | 0 ÷ 1 MHz |
Series impedance per line | 2.2 Ω | |
Parasitic capacitance | C | < 1.5 nF |
Lightning protection zone | LPZ 0-1, LPZ 1-2, LPZ 2-3, LPZ3 | |
Housing material | AlMgSi (EN AW 6060) | |
Degree of protection | IP20 | |
Operating temperature | ϑ | - 40 ÷ 70 °C |
Clamp fastening range (solid conductor) | 0.2 ÷ 2.5 mm2 | |
Tightening moment | 0,5 | |
Installation | On DIN rail 35 mm | |
Operating position | Any | |
Remote signalling | No | |
Pluggable version | No |