Testing category according to IEC 61643-21:2000 and EN 61643-21:2001
|
|
C1, C2, C3
|
Connector type
|
|
RJ45
|
Rated operating DC voltage
|
UN |
0 ÷ 48 V |
Maximum continuous operating voltage DC
|
UC |
58 V
|
Maximum continuous operating voltage AC
|
UC |
41 V
|
Rated load current
|
IL |
1 A
|
C1 Nominal discharge current (8/20) line/line
|
In |
0.15 kA
|
C2 Nominal discharge current (8/20)
|
In |
1 kA
|
C2 Voltage protection level at In (line/line)
|
Up |
< 150 V
|
C2 Voltage protection level at In (line/PE)
|
Up |
< 700 V
|
C3 Voltage protection level at 1 kV/μs
|
Up |
< 120 V
|
Data rate
|
|
500 Mbit/s
|
Bandwidth
|
B |
0 ÷ 500 MHz |
Lightning protection zone
|
|
LPZ 1-2, LPZ 2-3, LPZ3
|
Housing material
|
|
AlMgSi (EN AW 6060)
|
Degree of protection
|
|
IP20
|
Operating temperature
|
ϑ |
- 40 ÷ 70 °C |
Installation
|
|
On DIN rail 35 mm
|
Operating position
|
|
Any
|
Signalling at the device
|
|
None
|
Remote signalling
|
|
No |
Normative conformity
|
|
Kat. 6A/EA, ISO/IEC 11801
|
PoE
|
|
IEEE 802.3at
|