Testing category according to IEC 61643-21:2000 and EN 61643-21:2001
|
|
C1, C2, C3, D1
|
|
Connector type
|
|
RJ45
|
|
Maximum continuous operating voltage DC (line/line)
|
UC |
70 V
|
|
Maximum continuous operating voltage DC (line/G)
|
UC |
70 V
|
|
Maximum continuous operating voltage DC (PoE pair/pair)
|
UC |
70 V
|
|
Rated load current of line
|
IL |
1 A
|
|
Cut-off frequency (3 dB attenuation at Z0 = 100 Ω)
|
fC |
> 1 000 MHz
|
|
Transmission bandwidth
|
BW |
> 1 000 MHz
|
|
D1 Total impulse discharge current (10/350) line/G
|
ITotal |
1 kA
|
|
C2 Total nominal discharge current (8/20) line/G
|
ITotal |
10 kA
|
|
C1 Nominal discharge current (8/20) line/G
|
In |
0.25 kA
|
|
C2 Nominal discharge current (8/20) line/line
|
In |
1.25 kA
|
|
C2 Nominal discharge current (8/20) line/G
|
In |
1.25 kA
|
|
C2 Voltage protection level at In (line/line)
|
Up |
< 1 100 V
|
|
C2 Voltage protection level at In (line/G)
|
Up |
< 700 V
|
|
C2 Voltage protection level at In (PoE pair/pair)
|
Up |
< 1 150 V
|
|
C3 Voltage protection level at 1 kV/μs (line/line)
|
Up |
< 700 V
|
|
C3 Voltage protection level at 1 kV/μs (line/G)
|
Up |
< 450 V
|
|
C3 Voltage protection level at 1 kV/μs (PoE pair/pair)
|
Up |
< 750 V
|
|
Lightning protection zone
|
|
LPZ 1-2, LPZ 2-3, LPZ 0B-1
|
|
Housing material
|
|
AlMgSi (EN AW 6060)
|
|
Degree of protection
|
|
IP20
|
|
Operating temperature
|
ϑ |
- 40 ÷ 70 °C |
|
Installation
|
|
On DIN rail 35 mm
|
|
Operating position
|
|
Any
|
|
Signalling at the device
|
|
None
|
|
Remote signalling
|
|
No |
|
Suitable for use with cabling category according to ISO/IEC 11801
|
|
Cat.7A/FA
|
|
PoE standards
|
|
All
|