KO - 2P
Article number: 55 015- Designed for protection of equipment connected to an aerial system by means of coaxial cables.
- The products consist of gas discharge tube with high discharge ability, thanks to which ensure a reliable protection of the receiving and transmitting systems even against a lightning stroke nearby.
- Wide range or products, various connector types and transmission power grades.
- Recommended for use in the Lightning Protection Zones at the boundaries of LPZ 0 – LPZ 1 and higher.
| Testing category according to IEC 61643-21:2000 and EN 61643-21:2001 | C1, C2, C3, D1 | |
| Connector type | BNC | |
| Maximum continuous operating voltage DC | UC | 200 V |
| Rated load current | IL | 2.5 A |
| C2 Nominal discharge current (8/20) | In | 5 kA |
| C3 Voltage protection level at 1 kV/μs | Up | < 600 V |
| D1 Impulse discharge current (10/350) | Iimp | 2 kA |
| Maximum discharge current (8/20) | Imax | 10 kA |
| Frequency bandwidth | B | 0 ÷ 1 GHz |
| Max. transmission power capacity | 400 W | |
| Insertion loss | < 0.2 dB | |
| Return loss | > 20 dB | |
| Characteristic impedance | 50 Ω | |
| Degree of protection | IP20 | |
| Operating temperature | ϑ | - 30 ÷ 70 °C |