MDS-DELTA
Article number: 70 065- Remote monitoring panels for medical staff at monitoring stations.
- Display the status of Medical IT system (MIPS) monitored by HAKEL insulation monitoring devices.
- Display the current insulation status, or current and temperature overload of the isolating transformer.
- Modules are equipped with a STOP ALARM button to stop the acoustic fault signaling.
- Modules are equipped with a TEST button to initiate testing of signalization and internal circuits of the insulation monitoring device.
- Remote monitoring modules meet the standard requirements for supervision signaling of the Medical IT systems classified in the medical locations of group 2. This includes acoustic and optical signaling.
- Versions are available for surface mounting, mounting into an electrical back box and also in a 45 x 45 mm cable tray.
| Designed for an insulation monitoring device | HIG95, HIG95-DELTA | |
| Power source | External power supply SELV 24 V DC | |
| Nominal supply voltage DC | Us | 24 V |
| Visual signaling of insulation fault | Yes | |
| Visual signaling of thermal and current overload of the isolating transformer | Yes | |
| Acoustic fault signaling | Yes | |
| Possibility to stop the acoustic signaling | Yes | |
| Possibility to run a test of the insulation monitoring device | Yes | |
| Auxiliary signaling module to increase visual warning | No | |
| Maximum number of connectable insulation monitoring devices | 1 | |
| Degree of protection | IP20 | |
| Operating temperature | ϑ | - 5 ÷ 55 °C |
| Width | 45 mm | |
| Height | 45 mm | |
| Depth | 8.5 mm | |
| Power conductor stripping length | 6 | |
| Tightening torque | 0.2 | |
| Installation | For window cable duct 45 x 45 mm | |
| Operating position | Horizontal | |
| Method of connecting the insulation monitoring device | RS485 bus (ISOLGUARD protocol) | |
| Recommended cross-section of connecting wires | S | 0.75 ÷ 1 mm2 |
| Recommended fuse protection | 6 A/gG | |
| Power consumption | P | 0.5 VA |