PIIIM PV 800 DS Vseries
Article number: 27 059- Surge arresters type T2 intended for photovoltaic systems (PV).
- Products are designed in a Y-type connection, which is resistant to earth faults of working conductors.
- Particular varistor sectors, connected between the terminals L+, L- and PE are equipped with internal disconnectors, which are activated when the varistors fail (overheat) and they are able to interrupt the DC current.
- Special construction of the internal disconnector allows installation without a back-up fuse.
- They are installed in PV applications without an external LPS or with an external LPS, where the sufficient distance "s" is observed.
- Suitable for all LPL levels.
- Ensure the equipotential bonding of positive and negative busbars of PV systems and the elimination of transient overvoltage that originates during the atmospheric discharges or switching processes.
- M indication specifies a type of construction with removable module.
- DS indication specifies a version with remote monitoring.
Test class according to EN 61643-11:2012 and EN 61643-31:2019 | T2 | |
System | DC | |
PV system type | Ungrounded | |
SPD connection type | Y | |
Maximum continuous operating voltage (+/-) | UCPV | 870 V DC |
Maximum continuous operating voltage (±/PE) | UCPV | 870 V DC |
Max. voltage of PV generator UOCSTC ≤ UCPV / 1.2 | UOCSTC | 730 V |
Short-circuit current rating | ISCPV | 10 kA |
Maximum discharge current (8/20) | Imax | 40 kA |
Nominal discharge current for class II test (8/20) | In | 15 kA |
Voltage protection level at In | Up | < 3.3 kV |
Response time | tA | < 25 ns |
Housing material | Polyamid PA6, UL94 V-0 | |
Degree of protection | IP20 | |
Operating temperature | ϑ | - 40 ÷ 70 °C |
Humidity range | RH | 5 ÷ 95 % |
Minimum cross-section of connected Cu conductors according to IEC 61643-32:2017 (doesn't apply to „V“ connection) for T2 | S |
2.5 mm² (L+, L-) 6 mm² (PE) |
Clamp fastening range (solid conductor) | 2.5 ÷ 35 mm2 | |
Clamp fastening range (stranded conductor) | 2.5 ÷ 25 mm2 | |
Tightening moment | 4 | |
Installation | On DIN rail 35 mm | |
Modular width | 3 | |
Operating position | Any | |
Product placement environment | Internal | |
SPD failure mode | OCFM | |
Signalling at the device | Optic | |
Importance of local signaling |
OK – green target FAULT – red target |
|
Remote signalling | Yes | |
Potential free signal contact (S) (recommended cross-section of remote monitoring max. 1 mm2) | AC: 250 V / 1.5 A, DC: 250 V / 0.1 A | |
Pluggable version | Yes | |
Article number of spare module | 27 068 | |
Lifetime | > 100 000 h |