PIVM PV 1000/M Vseries
Article number: 16 078- Removable modules for lightning impulse current and surge arresters type T1+T2 intended for photovoltaic systems (PV).
- Contain a varistor with high discharge ability.
- Modules are equipped with internal disconnectors, which are activated when the varistors fail (overheat) and they are able to interrupt the DC current.
- Special construction of the internal disconnector allows installation without a back-up fuse.
- Ensure the equipotential bonding of plus and minus busbars of PV systems and the elimination of transient overvoltage resulting from the atmospheric discharges (including direct lightning strike to the PV system) or switching processes.
Impulse discharge current for class I test (10/350) | Iimp | 6.5 kA |
Test class according to EN 61643-11:2012 and EN 61643-31:2019 | T1, T2 | |
Maximum continuous operating voltage | UCPV | 1 000 V DC |
Maximum continuous operating voltage (+/-) | UCPV | 1 000 V DC |
Short-circuit current rating | ISCPV | 10 kA |
Nominal discharge current for class II test (8/20) | In | 15 kA |
Voltage protection level at In | Up | < 3.4 kV |
Spare module for | 16 076, 16 077 |