PIVM PV 600 Vseries
Article number: 16 070- Lightning impulse current and surge arresters type T1+T2 intended for photovoltaic systems (PV).
- Products are designed in a Y-type connection, which is resistant to earth faults of working conductors.
- Particular varistor sectors, connected between the terminals L+, L- and PE are equipped with internal disconnectors, which are activated when the varistors fail (overheat) and they are able to interrupt the DC current.
- Special construction of the internal disconnector allows installation without a back-up fuse.
- They are installed on the DC side in PV applications with external LPS, where a sufficient distance "s" is not observed.
- Suitable for level LPL III or IV.
- Ensure the equipotential bonding of plus and minus busbars of PV systems and the elimination of transient overvoltage resulting from the atmospheric discharges (including direct lightning strike to the PV system) or switching processes.
- M indication specifies a type of construction with removable module.
- DS indication specifies a version with remote monitoring.
Impulse discharge current for class I test (10/350) | Iimp | 6.5 kA |
Test class according to EN 61643-11:2012 and EN 61643-31:2019 | T1, T2 | |
System | DC | |
PV system type | Ungrounded | |
SPD connection type | Y | |
Maximum continuous operating voltage (+/-) | UCPV | 600 V DC |
Maximum continuous operating voltage (±/PE) | UCPV | 600 V DC |
Max. voltage of PV generator UOCSTC ≤ UCPV / 1.2 | UOCSTC | 500 V |
Short-circuit current rating | ISCPV | 10 kA |
Charge | Q | 3.25 As |
Specific energy for class I test | W/R | 10.56 kJ/Ω |
Maximum discharge current (8/20) | Imax | 40 kA |
Nominal discharge current for class II test (8/20) | In | 20 kA |
Voltage protection level at In (L+/L-) | Up | < 2.6 kV |
Response time | tA | < 25 ns |
Housing material | Polyamid PA6, UL94 V-0 | |
Degree of protection | IP20 | |
Operating temperature | ϑ | - 40 ÷ 70 °C |
Humidity range | RH | 5 ÷ 95 % |
Minimum cross-section of connected Cu conductors according to IEC 61643-32:2017 (doesn't apply to „V“ connection) for T1 | S |
6 mm² (L+, L-) 16 mm² (PE) |
Minimum cross-section of connected Cu conductors according to IEC 61643-32:2017 (doesn't apply to „V“ connection) for T2 | S |
2.5 mm² (L+, L-) 6 mm² (PE) |
Clamp fastening range (solid conductor) | 2.5 ÷ 35 mm2 | |
Clamp fastening range (stranded conductor) | 2.5 ÷ 25 mm2 | |
Tightening moment | 4 | |
Installation | On DIN rail 35 mm | |
Modular width | 3 | |
Operating position | Any | |
Product placement environment | Internal | |
SPD failure mode | OCFM | |
Signalling at the device | Optic | |
Importance of local signaling |
OK – green target FAULT – red target |
|
Remote signalling | No | |
Pluggable version | Yes | |
Article number of spare module | 16 072 | |
Lifetime | > 100 000 h |