PIVM12,5-275/4+0 Vseries

Article number: 16 056
  • Lightning impulse current and surge arresters type T1+T2 ensure the equipotential bonding, eliminate the effects of lightning current and reduce switching, induced and residual overvoltage in single-phase and three-phase power supply systems.
  • The products consist of varistors with big discharge ability.
  • Configurations 1+1 and 3+1 are additionally combined with a gas discharge tube which ensures zero leakage current through the PE conductor.
  • Suitable for objects with considerable levels of protection LPL III and LPL IV.
  • Installed at the boundaries of LPZ 0 – LPZ 1 and higher zones, closest to where overhead line enters the building i.e. in the main distribution boards.
  • M specifies a type of construction with removable module.
  • DS indication specifies a version with remote monitoring.
  • Other voltage levels can be produced on request.
Test class according to EN 61643-11:2012 (IEC 61643-11:2011) T1, T2
System TN-S
Number of poles
Rated operating AC voltage UN 230 V
Maximum continuous operating voltage AC UC 275 V
Maximum discharge current (8/20) Imax 50 kA
Impulse discharge current for class I test (10/350) Iimp 12.5 kA
Charge Q 6.25 As
Specific energy for class I test W/R 39 kJ/Ω
Total discharge current (10/350) L1+L2+L3+N->PE ITotal 50 kA
Total discharge current (8/20) L1+L2+L3+N->PE ITotal 200 kA
Nominal discharge current for class II test (8/20) In 20 kA
Voltage protection level at In Up < 1.2 kV
Temporary overvoltage test (TOV) for tT = 5 s UT 335 V
Response time tA < 25 ns
Maximal back-up fuse 160 A gL/gG
Short-circuit current rating at maximum back-up fuse ISCCR 60 kArms
Lightning protection zone LPZ 0-1, LPZ 1-2, LPZ 2-3
Housing material Polyamid PA6, UL94 V-0
Degree of protection IP20
Operating temperature ϑ - 40 ÷ 70 °C
Minimum cross-section of connected Cu conductors accord. to HD 60364-5-53:2022 (doesn't apply to „V“ connection) for T1 S 6 mm² (L, N)
16 mm² (PE, PEN)
Minimum cross-section of connected Cu conductors accord. to HD 60364-5-53:2022 (doesn't apply to „V“ connection) for T2 S 2.5 mm² (L, N)
6 mm² (PE, PEN)
Clamp fastening range (solid conductor) 2.5 ÷ 35 mm2
Clamp fastening range (stranded conductor) 2.5 ÷ 25 mm2
Tightening moment 4
Installation On DIN rail 35 mm
Modular width 4
Operating position Any
Signalling at the device Optic
Importance of local signaling OK – green target
FAULT – red target
Remote signalling No
Pluggable version Yes
Article number of spare module 16 058
Lifetime > 100 000 h
QUICK CONTACT
Quick contact
Ing. Aneta Sčebelová
 +420 494 942 314