PIVM12,5-275 IT DS/2+1 Vseries

Article number: 16 164
  • Lightning impulse current and surge arresters type T1+T2 ensure the equipotential bonding, eliminate the effects of lightning current and reduce switching, induced and residual overvoltage in single-phase IT power supply systems.
  • The products consist of varistors with big discharge ability with gas discharge tube, which ensures zero leakage current in the PE conductor.
  • Installed at the boundaries of zones LPZ 0 – LPZ 1 and higher closest to where the overhead line enters the building.
  • Suitable for objects with considerable levels of protection LPL III and LPL IV.
  • M specifies a type of construction with removable module.
  • DS indication specifies a version with remote monitoring.
  • Other voltage levels can be produced on request.
Test class according to EN 61643-11:2012 (IEC 61643-11:2011) T1, T2
System IT
Number of poles
Nominal line voltage UN 230 V
Maximum continuous operating voltage AC UC 275 V
Maximum discharge current (8/20) Imax 50 kA
Impulse discharge current for class I test (10/350) L/CP Iimp 12.5 kA
Charge (L/CP) Q 6.25 As
Specific energy for class I test (L/CP) W/R 39 kJ/Ω
Impulse discharge current for class I test (10/350) CP/PE Iimp 25 kA
Charge (CP/PE) Q 12.5 As
Specific energy for class I test (CP/PE) W/R 156 kJ/Ω
Total discharge current (10/350) L1+L2+CP->PE ITotal 25 kA
Nominal discharge current for class II test (8/20) In 25 kA
Voltage protection level at In Up < 2.5 kV
Temporary overvoltage test (TOV) for tT = 5 s (L/CP) UT 337 V
Temporary overvoltage test (TOV) for tT = 0.2 s (CP/PE) UT 1 200 V
Response time (L/CP) tA < 25 ns
Response time (CP/PE) tA < 100 ns
Maximal back-up fuse 160 A gL/gG
Short-circuit current rating at maximum back-up fuse ISCCR 60 kArms
Lightning protection zone LPZ 0-1, LPZ 1-2, LPZ 2-3
Housing material Polyamid PA6, UL94 V-0
Degree of protection IP20
Operating temperature ϑ - 40 ÷ 70 °C
Minimum cross-section of connected Cu conductors accord. to HD 60364-5-53:2022 (doesn't apply to „V“ connection) for T1 S 6 mm² (L, N)
16 mm² (PE, PEN)
Minimum cross-section of connected Cu conductors accord. to HD 60364-5-53:2022 (doesn't apply to „V“ connection) for T2 S 2.5 mm² (L, N)
6 mm² (PE, PEN)
Clamp fastening range (solid conductor) 2.5 ÷ 35 mm2
Clamp fastening range (stranded conductor) 2.5 ÷ 25 mm2
Tightening moment 4
Installation On DIN rail 35 mm
Modular width 3
Operating position Any
Signalling at the device Optic
Importance of local signaling OK – green target
FAULT – red target
Remote signalling Yes
Potential free signal contact (S) (recommended cross-section of remote monitoring max. 1 mm2) AC: 250 V / 1.5 A, DC: 250 V / 0.1 A
Pluggable version Yes
Article number of the varistor spare module 16 058
Article number of the gas discharge tube spare module 16 041
Lifetime > 100 000 h