WITHOUT LPS

If the building does not have an air termination system, there is no risk of a direct lightning strike to the building or PV system (impulse current with parameters of 10/350 µs). In this case we can install SPD type T2. HSA PV 600 M can be a suitable SPD representative at position A, or at positions A and D when the distance between the inverter and the panels is greater than 10 m. This product is determined specifically for UCPV = 600 V DC, but we also offer variants for 1 000 V DC and 1500 V DC. It is in Y connection, which is resistant to the earth fault of live conductors and has zero residual (leakage) current. If you insist on a cheaper option, we also offer variants in the full voltage range in U connection with a marking /2 at the end of the product name. The entire product range brings the advantage of an exchangeable module design - the products are marked with the letter M and meet the discharge capability for all LPL levels. It is equipped with an internal DC arc fault disconnector and therefore no back-up fuse is required. If remote monitoring of the surge protection status is required, the variants marked S can be used, i.e. for example HSA PV 600 M S. The potential-free contact of this remote monitoring is then connected to the building‘s control system (typically as an input of a PLC control system), where it permanently informs the investor about the status of the surge protection device, without the need for physical control of the switchboard.

Unless otherwise specified in the risk assessment, a suitable representative of the SPD in position C can be a SPD type T2, for example HSA-275/3+0 M S, assuming an electrical distribution of 3 x 230 V / 50 Hz, in a TN-C configuration. The marking M specifies the design with exchangeable module, S specifies the design with remote monitoring. If the entire electrical distribution of the building is TN-S, the HSA-275/4+0 M S configuration can be used. If we consider a three-phase TN-S system, a suitable representative is, for example, HSA-275/3+1 M S. The entire range of SPDs for the AC side is also available in an unchangeable design.

image/svg+xml Grid SPD DC SPD DC SPD AC Main earthing bar Subsidiary earthing bar SPD AC > 10 m > 10 m PV array PV inventer Main distribution board Subsidiary earthing bar A SPD FOR DC (INVERTER) B SPD FOR AC (INVERTER) C SPD FOR AC D SPD FOR DC

Our solutions

  1. SPD FOR DC (INVERTER)
    Nahrávám ...
    By ticking this box you will give us the information that you are not sure about the correctness of your selection. However, it is necessary to send an inquiry.
  2. SPD FOR AC (INVERTER)
    Nahrávám ...
    By ticking this box you will give us the information that you are not sure about the correctness of your selection. However, it is necessary to send an inquiry.
  3. SPD FOR AC
    Nahrávám ...
    By ticking this box you will give us the information that you are not sure about the correctness of your selection. However, it is necessary to send an inquiry.
  4. SPD FOR DC
    Nahrávám ...
    By ticking this box you will give us the information that you are not sure about the correctness of your selection. However, it is necessary to send an inquiry.