HDSP CAN/12

Article number: 56 052
  • Two-stage surge protection of connected CAN bus device.
  • They are installed prior to the protected equipment and at the interface of LPZs 1 – 2 and higher.
  • They increase the EMC level of the connected equipment against switching and atmospheric transients.
  • The connection of the module allows to use the operating range of CAN bus drivers in the range of +/- 12 V (common-mode voltage range).
  • Connecting the module allows the full CAN bus speed of 1 Mb/s to be used.
  • They provide cable shield protection by limiting pulse overvoltage through a built-in 90 V gas discharge tube.
Testing category according to IEC 61643-21:2000 and EN 61643-21:2001 C2, C3, B3
Number of pairs 1
Connector type Screw terminals
Rated operating voltage DC of data line X1-5, X3-5 UN 0 ÷ 12 V
Maximum continuous operating voltage DC of data line X1-5, X3-5 UC 15 V
Maximum continuous operating voltage DC X5-9, X7-9 UC 70 V
Rated load current of data line X1-2, X3-4 IL 0.5 A
C2 Nominal discharge current (8/20) In 5 kA
C2 Voltage protection level X2-6, X4-6 at In Up < 32 V
C2 Voltage protection level X2-4 at In Up < 56 V
C3 Voltage protection level X2-6, X4-6 at 1 kV/μs Up < 20 V
C3 Voltage protection level X2-4 at 1 kV/μs Up < 40 V
B3 Voltage protection level X6-10, X8-10 at 100 V/μs Up < 550 V
C3 Voltage protection level X6-10, X8-10 at 1 kV/μs Up < 700 V
Serial resistance of data line X1-2, X3-4 R 1.6 Ω
Capacitance X2-4 at 0 V C 150 pF
Limiting transmission frequency S21 for Z0 = 120 Ω fC 16 MHz
Lightning protection zone LPZ 1-2, LPZ 2-3, LPZ3
Housing material Polyamid PA6, UL94 V-0
Degree of protection IP20
Operating temperature ϑ - 40 ÷ 70 °C
Clamp fastening range (solid conductor) 0.2 ÷ 4 mm2
Tightening moment 0,5
Installation On DIN rail 35 mm
Operating position Any
Remote signalling No
Modular design No