Testing category according to IEC 61643-21:2000 and EN 61643-21:2001
|
|
C2, C3, B3
|
Number of pairs
|
|
1
|
Connector type
|
|
Screw terminals
|
Rated operating voltage DC of data line X1-7, X3-7
|
UN |
0 ÷ 12 V |
Maximum continuous operating voltage DC of data line X1-7, X3-7
|
UC |
15 V |
Rated operating voltage DC of power line X5-7
|
UN |
0 ÷ 24 V |
Maximum continuous operating voltage DC of power line X5-7
|
UC |
30 V
|
Maximum continuous operating voltage DC X7-9
|
UC |
70 V
|
Rated load current of power line X5-6
|
IL |
5 A
|
Rated load current of data line X1-2, X3-4
|
IL |
0.5 A
|
C2 Nominal discharge current (8/20)
|
In |
5 kA
|
C2 Voltage protection level X2-8, X4-8 at In
|
Up |
< 32 V
|
C2 Voltage protection level X2-4 at In
|
Up |
< 56 V
|
C2 Voltage protection level X6-8 at +In
|
Up |
< 43 V
|
C2 Voltage protection level X6-8 at -In
|
Up |
> - 10 V
|
C3 Voltage protection level X2-8, X4-8 at 1 kV/μs
|
Up |
< 20 V
|
C3 Voltage protection level X2-4 at 1 kV/μs
|
Up |
< 40 V
|
C3 Voltage protection level X6-8 at +1 kV/μs
|
Up |
< 40 V
|
C3 Voltage protection level X6-8 at -1 kV/μs
|
Up |
> - 1 V
|
B3 Voltage protection level X8-10 at 100 V/μs
|
Up |
< 550 V
|
C3 Voltage protection level X8-10 at 1 kV/μs
|
Up |
< 700 V
|
Serial inductance of X5-6 power line
|
L |
2.2 μH
|
Serial resistance of data line X1-2, X3-4
|
R |
1.6 Ω
|
Capacitance X2-4 at 0 V
|
C |
150 pF
|
Limiting transmission frequency of data link S21 for Z0=120 Ω
|
fC |
16 MHz
|
Lightning protection zone
|
|
LPZ 1-2, LPZ 2-3, LPZ3
|
Housing material
|
|
Polyamid PA6, UL94 V-0
|
Degree of protection
|
|
IP20
|
Operating temperature
|
ϑ |
- 40 ÷ 70 °C |
Clamp fastening range (solid conductor)
|
|
0.2 ÷ 4 mm2 |
Tightening moment
|
|
0,5
|
Installation
|
|
On DIN rail 35 mm
|
Operating position
|
|
Any
|
Remote signalling
|
|
No |
Pluggable version
|
|
No |