HDT1/48D
Article number: 56 037- Designed for the protection of data and communication lines against longitudinal and transverse surge effects.
- Pluggable version.
- No interruption of communication bus when the module is removed.
- One pair or two pairs lines.
- Contains both 1st and 2nd stage of protection.
- High transmission speed up to 100 Mbit/s.
- Suitable for use in industrial applications, especially in low-voltage ESS, FDAS systems and also in measurement and control systems.
| Testing category according to IEC 61643-21:2000 and EN 61643-21:2001 | C1, C2, C3, D1 | |
| Number of pairs | 1 | |
| Connector type | Screw terminals | |
| Rated operating DC voltage | UN | 0 ÷ 48 V |
| Maximum continuous operating voltage DC | UC | 57.6 V |
| Rated load current | IL | 0.5 A |
| C1 Voltage protection level at In (line/PE) | Up | < 500 V |
| C1 Voltage protection level at In (line/line) | Up | < 220 V |
| C1 Nominal discharge current (8/20) | In | 1 kA |
| C2 Voltage protection level at In (line/PE) | Up | < 260 V |
| C2 Voltage protection level at In (line/line) | Up | < 240 V |
| C2 Nominal discharge current (8/20) | In | 15 kA |
| C3 Voltage protection level at 1 kV/μs | Up | < 70 V |
| D1 Impulse discharge current (10/350) line/PE | Iimp | 2.5 kA |
| D1 Total impulse discharge current (10/350) | ITotal | 5 kA |
| Response time | tA | < 30 ns |
| Data rate | 100 Mbit/s | |
| Bandwidth | B | 0 ÷ 100 MHz |
| Series impedance per line | 0.8 Ω | |
| Parasitic capacitance | C | < 0.04 nF |
| Lightning protection zone | LPZ 0-1, LPZ 1-2, LPZ 2-3 | |
| Housing material | Polyamid PA6, UL94 V-0 | |
| Degree of protection | IP20 | |
| Operating temperature | ϑ | - 40 ÷ 55 °C |
| Clamp fastening range (solid conductor) | 0.2 ÷ 1.5 mm2 | |
| Tightening torque | 0.5 | |
| Installation | On DIN rail 35 mm | |
| Modular width | 1 | |
| Operating position | Any | |
| Remote signalling | No | |
| Pluggable version | Yes | |
| Article number of spare module | 56 037/M | |
| Lifetime | > 100 000 h |