HIG-CD 3k6

Article number: 70 984
  • It is necessary to observe the use of the appropriate coupling unit for the specific insulation monitoring device.
  • The coupling devices HIG-CD are used to adapt the input circuits of the insulation monitoring device to a higher operating voltage than the operating voltage of the IMD directly.
  • The coupling devices are connected between the insulated system and the insulation monitoring device.
Rated operating AC voltage UN 2 500 V
Rated operating DC voltage UN 3 600 V
Maximum continuous operating voltage AC UC 2 500 V
Maximum continuous operating voltage DC UC 3 600 V
Designed for insulation monitoring device HIG99/3k6
Internal resistance RIN 2 x 900
Offset for insulation monitoring device Rtl ext 900 kΩ
Use for traction Yes
Housing material Aluminium, Electroinsulating potting compound
Degree of protection IP65, except for connecting wires
Operating temperature ϑ - 40 ÷ 70 °C
Cable length l 2 m
Recommended cross-section of connected conductors S 2.5 mm2
Tightening moment 1,2
Installation On the mounting plate
Operating position Any
Operation type Permanent
Lifetime > 100 000 h