HIG-MT 50/5 A
Article number: 71 533- Used to sense the current load of a medical insulated power supply system, which is monitored by the insulation monitoring device from HAKEL.
- Available in the range of primary current 25 A to 100 A, secondary current 5 A.
- Construction is pluggable, is supplied in two dimensional versions, depending on the primary current.
- Designed for installation in an IPS panel, they can be mounted to the distribution board using reduction brackets (included), or using a DIN rail bracket (must be purchased separately).
- Alternatively, the transformer can be mounted directly on the copper profile, up to a maximum size of 20 x 10 mm.
- Work reliably with HAKEL HIG95-DELTA and HIG95+ insulation monitoring devices.
Primary current | 50 A | |
Secondary side current | 5 A | |
Power | P | 1 W |
Accuracy class | 1 | |
Overcurrent number (FS) | 10 | |
Transformer construction | Pluggable (without interrupting the primary conductor) | |
Frequency | f | 50 ÷ 60 Hz |
Housing material | Self-extinguishing | |
Recommended cross-section of connected conductors | S | 1.5 ÷ 2.5 mm2 |
Operating position | Any | |
Operating temperature | ϑ | - 25 ÷ 40 °C |
Article number of DIN rail bracket | 71 541 |